Images are representations only.

Series AT2605 ATEX/IECEx Approved 605 Differential Pressure Transmitter

Brand: Dwyer Instruments, LLC
Does not ship to VA, United States
The ATEX/IECEx approved Series AT2605 Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure in hazardous locations.

The easily read dial gauge is complimented by the two-wire, 4 to 20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gauge mechanical design and Series 600 transmitter technology. 

The two-wire design simplifies any 4 to 20 mA control loop powered by a 10 to 35 VDC supply. Flame-proof enclosures are available in aluminum and can include a glass window for viewing process pressure on gauge face.

Important notes for installation:
  • Cables must be fitted through 1/2" NPT cable gland or ATEX/IECEx conduit (not supplied with instrument).
  • Make sure after cabling to close tight cover and cable gland, in order to keep IP66 rating (IP65 with option OPV, overpressure relief valve).
  • Open cover only after de-energizing instrument.
  • Attention: Check local safety rules and warnings on unit and manual for a correct use of the instrument in hazardous area.
Features
  •  ATEX housing provides all the capabilities and value of the Magnehelic 605 in a flame & explosion proof enclosure
  • Quick response to pressure changes means no delay in assessing critical situations
  • Durable and rugged housing and high-quality components combined provides longservice life and minimized down-time
  • High impact strength and high temperature rated for applications where hazardous environments exist
The ATEX/IECEx approved Series AT2605 Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure in hazardous locations.

The easily read dial gauge is complimented by the two-wire, 4 to 20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gauge mechanical design and Series 600 transmitter technology. 

The two-wire design simplifies any 4 to 20 mA control loop powered by a 10 to 35 VDC supply. Flame-proof enclosures are available in aluminum and can include a glass window for viewing process pressure on gauge face.

Important notes for installation:
  • Cables must be fitted through 1/2" NPT cable gland or ATEX/IECEx conduit (not supplied with instrument).
  • Make sure after cabling to close tight cover and cable gland, in order to keep IP66 rating (IP65 with option OPV, overpressure relief valve).
  • Open cover only after de-energizing instrument.
  • Attention: Check local safety rules and warnings on unit and manual for a correct use of the instrument in hazardous area.
Features
  •  ATEX housing provides all the capabilities and value of the Magnehelic 605 in a flame & explosion proof enclosure
  • Quick response to pressure changes means no delay in assessing critical situations
  • Durable and rugged housing and high-quality components combined provides longservice life and minimized down-time
  • High impact strength and high temperature rated for applications where hazardous environments exist

Specifications

Accuracy

  • ± 0.5 % of Full Scale (The Effects of Linearity, Hysteresis & Repeatability, are included)

Approvals & Certifications

  • ATEX Approved Products from Comhas with ECN: BVI 14-ATEX-0072
  • CE 1370 II2 GD Ex d IIC Gb T6, -60° C ≤ Ta ≤ +60° C Ex Tb IIIC Db T 85° C

Compensated Temperature

  • 0° to 48.9° C (32° to 120° F)

Connection Material

  • Brass
  • Stainless Steel

Consumption

  • DC: 38 mA - Max.

Cover Material

  • Glass Cover

Electrical Connectors

  • Screw Typical Terminal Block
  • Two 1/2” NPT Female

Enclosure Finish

  • Texture Epoxy Coat RAL7038

Enclosure, Body Material

  • Aluminum

Environmental Protection

  • IP65 with Option OPV
  • IP66

Loop Resistance

  • 0 to 1250 ohms, Max.

Media

  • Air
  • Non-Combustible & Compatible Gases

NPT Connection

  • 1/2” NPT Female
  • 1/8” NPT Female

Output

  • 4-20 mA

Power Requirement

  • 10 to 35 Vdc (2-Wire)

Pressure Range

  • Inches WC: 0 to 50
  • Pa: 0 to 500

Pressure Type

  • Gauge

Sensor Orientation

  • Diaphragm in Vertical Position

Size

  • Dial: 4” (100 mm)

Span & Zero Adjustments

  • Protected Potentiometers

Stability

  • ± 1 % of Full Scale Per Year

Temperature Effect

  • ± 0.025 % of Full Scale/°F (0.045 % of Full Scale/°C)

Temperature Range

  • -60° to 60° C (-76° to 140° F)

Applications

  • Monitor pressures in ducts, rooms, or total building pressures
  • Filter monitoring
  • Local indication of clean room pressures with process signal sent to control room
  • Hazardous area pressure measurement and transmitter