Images are representations only.

Series 442 Programmable HART® Temperature Transmitter

Brand: Pyromation
Does not ship to OH, United States
The Series 442 programmable HART® temperature transmitter is a 2-wire transmitter with an analog output.
 
It has measurement input for resistance thermometers (RTD) in 2-, 3- or 4-wire connections, thermocouples, resistance and voltage inputs. The transmitter can be programmed with a PC or HART® protocol hand-held terminal. 
 
These small units can be mounted in Pyromation DIN (Form B) connection heads, or they can be used for surface mounting by using a 35 mm DIN-rail mounting clip.

Features

  • Universal settings with HART® protocol for various signals.
  • Galvanic isolation
  • 2-wire technology, (4 to 20) mA analog output
  • High accuracy in total ambient temperature range
  • Fault signal on sensor break or short circuit
  • RFI/EMI Protected, CE marked
  • cURus, UL Recognized Component
  • FM Intrinsically safe and non-incendive for hazardous locations
  • Output simulation
The Series 442 programmable HART® temperature transmitter is a 2-wire transmitter with an analog output.
 
It has measurement input for resistance thermometers (RTD) in 2-, 3- or 4-wire connections, thermocouples, resistance and voltage inputs. The transmitter can be programmed with a PC or HART® protocol hand-held terminal. 
 
These small units can be mounted in Pyromation DIN (Form B) connection heads, or they can be used for surface mounting by using a 35 mm DIN-rail mounting clip.

Features

  • Universal settings with HART® protocol for various signals.
  • Galvanic isolation
  • 2-wire technology, (4 to 20) mA analog output
  • High accuracy in total ambient temperature range
  • Fault signal on sensor break or short circuit
  • RFI/EMI Protected, CE marked
  • cURus, UL Recognized Component
  • FM Intrinsically safe and non-incendive for hazardous locations
  • Output simulation

Specifications

Connection Type

  • 2-Wire
  • 3-Wire
  • 4-Wire

Current Limit

  • ≤ 23 mA

Output Signal

  • 4-20 mA or 20-4 mA

Transmission as

  • Temperature Linear
  • Resistance Linear
  • Voltage Linear

Switch on Delay

  • 4 s

Certifications & Approvals

  • FM
  • CSA
  • cURus
  • CE
  • EMC

RFI/EMI

  • Yes

Measurement Range

  • RTD: -200° to 850° C (-328° to 1,562° F)
  • Thermocouples (TC): -270° to 2,495° C (-454° to 4,523° F)
  • Resistance: 10 to 2,000 Ω
  • Millivolt (mV): -10 to 75 mV

Measurement Accuracy

  • Type K, J, T, E, L, U: ± 0.5° C or 0.08%
  • Type N, C, D: ± 1.0° C or 0.08%
  • Type B: ± 2.0° C or 0.08%
  • Type S, R: ± 1.4° C or 0.08%
  • Millivolt (mV): ± 20 µV or 0.08%

General Accuracy

  • Influence of Power Supply: ± 0.01%/V Deviation from 24 V
  • Load Influence: ± 0.02%/100 Ω
  • Long Term Stability: ≤ 0.1° C/year or ≤ 0.05%/year

Ambient Temperature

  • -40° to 85° C (-40° to 185° F)

Storage Temperature

  • -40° to 100° C (-40° to 212° F)

Vibration Protection

  • 4 g / (2 to 150) Hz according to IEC 60 068-2-6

EMC Immunity

  • Interference immunity and interference emission as per EN 61 326-1 (IEC 1326)

Review this product and let us know your experiences