Images are representations only.

Series 607D DIN Rail Mount Differential Pressure Transmitter

Brand: Dwyer Instruments, LLC
Does not ship to OH, United States
Series 607D DIN Rail Mount Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal.

The 607D housing is specifically designed to mount on a 35 mm DIN rail in a panel. This mounting style allows for several units to be mounted closely together reducing required space. 

A wide range of models are available factory calibrated to 0.25% full scale accuracy in ranges from 0.1 to 25 Inches WC. The span and zero controls are for field calibration.

Units also include red/green LED status of proper transmitter operation. Versatile circuit design enables operation in 2-wire current loops.
Features
  • High accuracy at low pressure ranges provides exceptional measurement for insuring tight-control and minimizing costly out of specification conditions
  • DIN mountable allows use in control panels for easy access to electrical supply reducing costly cabling
  • Visual LED indicators provides quick status on transmitter operation saving troubleshooting time
Series 607D DIN Rail Mount Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal.

The 607D housing is specifically designed to mount on a 35 mm DIN rail in a panel. This mounting style allows for several units to be mounted closely together reducing required space. 

A wide range of models are available factory calibrated to 0.25% full scale accuracy in ranges from 0.1 to 25 Inches WC. The span and zero controls are for field calibration.

Units also include red/green LED status of proper transmitter operation. Versatile circuit design enables operation in 2-wire current loops.
Features
  • High accuracy at low pressure ranges provides exceptional measurement for insuring tight-control and minimizing costly out of specification conditions
  • DIN mountable allows use in control panels for easy access to electrical supply reducing costly cabling
  • Visual LED indicators provides quick status on transmitter operation saving troubleshooting time

Specifications

Accuracy

  • ± 0.25 % of Full Scale at Room Temperature (RSS Includes Non-Linearity, Hysteresis & Non-Repeatability)

Approvals & Certifications

  • CE

Compensated Temperature

  • -18° to 77° C (0° to 170° F)

Electrical Connectors

  • Removable Terminal Block

Loop Resistance

  • DC: 0 to 800 ohms

Media

  • Air
  • Non-Conductive, Non-Corrosive Gases

NACE & NIST

  • NIST Traceable Calibration Certificate

Operating Temperature

  • -18° to 77° C (0° to 170° F)

Output

  • 4-20 mA

Power Requirement

  • 16-32 Vdc

Pressure Range

  • Inches WC: 0 to 25

Pressure Type

  • Differential

Process Connection Material

  • Rubber
  • Vinyl Tubing

Response Time

  • Approximately 10 milliseconds

Sensor Orientation

  • Vertical, on a 1.378” (35 mm) DIN Rail

Span & Zero Adjustments

  • Potentiometer for Zero

Stability

  • ± 1 % of Full Scale Per Year

Storage Temperature

  • -54° to 85° C (-65° to 185° F)

Temperature Effect

  • Span: ± 0.01 % of Full Scale/°F at -7° to 77° C (20° to 170° F)
  • Zero: ± 0.01 % of Full Scale/°F at -7° to 77° C (20° to 170° F)

Tube Connection

  • 1/8” Tube

Wetted Materials

  • 302 Stainless Steel
  • Brass
  • Glass
  • Nickel
  • Silicone Rubber

Applications

  • HVAC
  • Clean room control
  • Filter status