Images are representations only.

Series 607D DIN Rail Mount Differential Pressure Transmitter

Brand: Dwyer Instruments, LLC
Does not ship to United States
Series 607D DIN Rail Mount Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal.

The 607D housing is specifically designed to mount on a 35 mm DIN rail in a panel. This mounting style allows for several units to be mounted closely together reducing required space.

A wide range of models are available factory calibrated to 0.25% full scale accuracy in ranges from 0.1 to 25 Inches WC. The span and zero controls are for field calibration.

Units also include red/green LED status of proper transmitter operation. Versatile circuit design enables operation in 2-wire current loops.
Features
  • High accuracy at low pressure ranges provides exceptional measurement for insuring tight-control and minimizing costly out of specification conditions
  • DIN mountable allows use in control panels for easy access to electrical supply reducing costly cabling
  • Visual LED indicators provides quick status on transmitter operation saving troubleshooting time
show more
Series 607D DIN Rail Mount Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal.

The 607D housing is specifically designed to mount on a 35 mm DIN rail in a panel. This mounting style allows for several units to be mounted closely together reducing required space.

A wide range of models are available factory calibrated to 0.25% full scale accuracy in ranges from 0.1 to 25 Inches WC. The span and zero controls are for field calibration.

Units also include red/green LED status of proper transmitter operation. Versatile circuit design enables operation in 2-wire current loops.
Features
  • High accuracy at low pressure ranges provides exceptional measurement for insuring tight-control and minimizing costly out of specification conditions
  • DIN mountable allows use in control panels for easy access to electrical supply reducing costly cabling
  • Visual LED indicators provides quick status on transmitter operation saving troubleshooting time

Specifications

Accuracy

  • ± 0.25 % of Full Scale at Room Temperature (RSS Includes Non-Linearity, Hysteresis & Non-Repeatability)

Approvals & Certifications

  • CE

Compensated Temperature

  • -18° to 77° C (0° to 170° F)

Electrical Connectors

  • Removable Terminal Block

Loop Resistance

  • DC: 0 to 800 ohms

Media

  • Air
  • Non-Conductive, Non-Corrosive Gases

NACE & NIST

  • NIST Traceable Calibration Certificate

Operating Temperature

  • -18° to 77° C (0° to 170° F)

Output

  • 4-20 mA

Power Requirement

  • 16-32 Vdc

Pressure Range

  • Inches WC: 0 to 25

Pressure Type

  • Differential

Process Connection Material

  • Rubber
  • Vinyl Tubing

Response Time

  • Approximately 10 milliseconds

Sensor Orientation

  • Vertical, on a 1.378” (35 mm) DIN Rail

Span & Zero Adjustments

  • Potentiometer for Zero

Stability

  • ± 1 % of Full Scale Per Year

Storage Temperature

  • -54° to 85° C (-65° to 185° F)

Temperature Effect

  • Span: ± 0.01 % of Full Scale/°F at -7° to 77° C (20° to 170° F)
  • Zero: ± 0.01 % of Full Scale/°F at -7° to 77° C (20° to 170° F)

Tube Connection

  • 1/8” Tube

Wetted Materials

  • 302 Stainless Steel
  • Brass
  • Glass
  • Nickel
  • Silicone Rubber

Typical Applications

  • HVAC
  • Clean room control
  • Filter status